Attach the enclosure to a wall or other structure using the customer supplied 3/8 inch
fasteners, flat washers and nuts. To ensure that the unit maintains proper sealing, it is very
important to be sure that the fasteners, washer and nuts are tightened thoroughly.
Note: Loose fasteners, washers and nuts may not provide proper sealing and /or securing of
the unit.
(Figure 7)
Electrical Wiring
NOTE
All electrical connections should be made by a licensed electrician. All local and National
codes should be followed as applicable.
Circuit Requirements
The TWSD16128PHC-UL should be connected to a 120V, 15A feeder circuit.
The maximum capacity of the power receptacle in the unit is 120V, 12A.
The circuit breaker of the feeder circuit is considered to be the disconnect device for
TWSD16128PHC-UL. Therefore, this circuit breaker should be readily accessible.